Water Slurry Electromagnetic Flow Meter

Water Slurry Electromagnetic Flow Meter

If any questions pls contact:michael@shboqu.com

4.1The flowmeter is compliant to Standard “JB/T 9248-1999 Electromagnetic Flow Meter”.
4.2Maximum flow speed: 15m/s
4.3DN size: 3, 6, 10, 15, 20, 25, 32, 40, 50, 65, 80, 100, 150, 200, 250, 300, 350, 400, 450, 500, 600, 700, 800, 900, 1000, 1200, 1400, 1600, 1800, 2000
4.4Accuracy: 0.5%, 0.2%
4.5Nominal Pressure: 4.0MPa(DN0-150)
1.6MPa(DN200-600)
1.0MPa(DN700-1200)
0.6MPa(DN400-2000)
Or other specified by order
4.6Materials
Electrode Forms and Materials:
Electrode design has four forms: standard form, scraper form, detachable form and grounding electrode.
Electrode material is selectable from stainless steel containing Mo, stainless steel coated with carbonized tungsten, Hastelloy B, Hastelloy C, Titanium, Tantalum and platinum-iridium alloy.
Flange material: carbon steel
Grounding ring: stainless steel
Inlet protection ring: carbon steel, stainless steel
4.7Enclosure
IP65:
IP68: only available for remote-type sensor with neoprene or polyurethane liner, not including flameproof model.
4.8Flameproof Standard
DN15-DN600 compact-type: md II BT4
DN15-DN1600 remote-type: sensor and converter both installed in dangerous area: md II BT4.
DN15-DN1600 remote-type: sensor installed in dangerous area and converter installed in safe area: md II BT4
4.9Connection Cable
Special cable is needed to connect the sensor and the converter for remote-type flowmeter. The cable length should not exceed 100 meters. A 10-meter cable is supplied free of charge and the rest is to be ordered.

4.10General Specification of Converter
Power supply: AC 85-265V, 45-63Hz, ≤20W;  DC 11-40V
Converter display and operation: four keys are available to set all parameters. External handheld or PC can be used to do the configuration. High resolution LCD display with backlight, empty pipe detection and self-diagnostic function are equipped in the converter.
Digital communication: RS485, RS232, MODBUS,REMOTE
Output Signals:
- Current output: fully-isolated, 4-20mA/0-10mA
load resistance: 0-10mA: 0-1.5KΩ; 4-20mA: 0-750Ω.
- Frequency output: bidirectional flow output. Frequency output is proportional to the flow percentage of the full range. The converter provides fully isolated transistor open collector frequency output ranged from 1 to 5000 Hz. The external DC power supply should not exceed 35V and maximum collector current is 250mA.
- Pulse output: bidirectional flow output. The converter can output up to 5000cp/s pulse series, which is dedicated to external totalization. Pulse factor is defined as volume or mass per pulse. It can be set to 0.001L/p, 0.01L/p, 0.1L/p, 1L/p, 2L/p, 5L/p, 10L/p, 100L/p, 1m3/p, 10 m3/p, 100 m3/p or 1000 m3/p. Pulse width is selectable from auto, 10ms, 20ms, 50ms, 100ms, 150ms, 200ms, 250ms, 300ms, 350ms and 400ms. Photo-coupler isolated transistor open collector circuit is used for pulse output. The external DC power supply should not exceed 35V and maximum collector current is 250mA.
- Flow direction indication: The converter is capable of measuring both forward and reverse flow and recognizing its direction. The converter outputs 0V low level for forward flow, while +12V high level for reverse flow.
- Alarm output: Two channels of photo-coupler isolated open collector circuit are used for alarm signal output. There are two alarm outputs: high limit alarm and low limit alarm. The external DC power supply should not exceed 35V and maximum collector current is 250mA.
- Damping constant: Damping time is selectable from 0.2 to 100s.

评论

此博客中的热门博文

SJG-2083C INDUCTIVE ACID ALKALI CONCENTRATION METER

CODS-3000-1 DIGITAL RS485 COD SENSOR

AH-800 Online Water Hardness and Alkali Analyzer